TECHNICAL SPECIFICATION |
Tower Model |
T-6000 |
19” Rack-mount Model |
TR-6000 |
Power Rating |
6kVA/4.2kW |
Input |
Voltage Frequency Phase Power factor |
110-300Vac at 50% Load, 220Vac ±20% at 100% load (±27% Option) 50Hz ±10% Single phase with ground >0.99 @ nominal voltage (100% Load) |
Output |
Voltage Voltage regulation Frequency Overload recovery UPS Design technology Crest factor Harmonic distortion Output waveform Transfer time |
208/220/230/240Vac ±1% 50 or 60Hz ±0.1% (Battery mode) Auto transfer to UPS True on-line double conversion, Full digitized microprocessor controlled 3 : 1 ≤3% THD (Linear load), ≤6% THD (Non-Linear load) Pure sinewave 0 ms |
Efficiency |
AC mode Battery mode ECO mode |
>89% >88% >95% |
Protection and Filtering |
Surge protection Overload protection Short circuit protection |
220V (IEEEC6100-4-5 level 3) UPS Automatic bypass if overload between 110% to 130% at 60 seconds and more than 130% at 1 seconds UPS Output cut off immediately or input fuse/circuit breaker protection |
Battery |
Type Typical recharge time to 90% Management Battery protection Cold Start (DC start) Back up time Expansion back up time |
Sealed, Maintenance-free lead acid batteries 8 hours Self-test, Adjustable battery transfer points and alarm setting Cut off without draining any current when battery is low Yes 15-30 minutes (Depending on computer load) Depending on customer required |
Indicators |
Status |
UPS status, Load level, Battery level, Input/output voltage, Discharge timer, and Fault conditions |
Audible Alarm |
Battery mode Low battery Overload Fault |
Sounding every 4 seconds Sounding every second Sounding twice every second Continuously sounding |
Dimension (DxWxH mm) |
Tower |
592 x 250 x 576 |
19” Rack-mount |
580 x 438 x 133 (3U) |
Weight (kg) |
Tower (with battery) |
81 |
19” Rack-mount (without battery) |
17 |
Environmental |
Operating temperature Relative humidity Noise level |
0-40 °c 0-95% (Non-Condensing) <45dB@1 Meter |
Interface |
Smart RS232 USB SNMP(Option) |
Software supports windows family, Linux, Sun solarris, IBM aix, Compaq true64, SGI IRIX, FreeBSD, HP-UX and MAC Windows family and MAC OS Power management from SNMP manager and web browser |