MODEL |
G-4300TLS |
RATED POWER |
DC input |
3.1 kW |
AC output |
3.0 kW |
SYSTEM |
Topology |
Transformerless |
DC INPUT
|
Nominal DC voltage |
380 Vdc |
MPPT voltage range (Vmp) |
100 - 490 Vdc |
Maximum DC voltage (Voc) |
500 Vdc |
Start-up voltage |
120 Vdc |
Maximum input current |
13 A |
Number of MPPTs / Strings per MPPT |
1 / 1 |
AC OUTPUT |
Voltage |
220 Vac (L-N) (for PEA grid line; “(P)” suffix in model name) 230 Vac (L-N) (for MEA grid line; “(M)” suffix in model name) |
Phase |
Single phase |
Frequency |
50 / 60 Hz |
Maximum output current |
13 A |
Power factor |
0.9 leading to 0.9 lagging |
Total harmonic distortion |
THDi < 3% |
EFFICIENCY |
Peak efficiency |
97.6% |
EURO efficiency |
97.0% |
PROTECTION |
Reverse polarity |
yes |
DC switch |
yes |
Ground fault detection |
yes |
Grid monitoring |
yes |
AC Short circuit |
yes |
Over voltage |
yes |
Over current |
yes |
Active anti-islanding |
yes |
INDICATOR |
LED |
Inverter status, Fault |
LCD display |
Inverter staus, Power, Today generated energy, Total generated energy, Grid line voltage / current / frequency, Power factor, Total run time, PV voltage and current, Fault |
COMMUNICATION |
Communication port |
RS-485 |
INTERFACE |
Optional |
RS-485 |
ACOUSTIC NOISE |
At 1 metre |
≤ 25 dBA |
ENVIRONMENT |
Temperature |
- 25˚C to 60˚C |
Humidity |
0 - 95 % (non - condensing |
DESIGN REGULATION |
Standard |
IEC 61727, IEC 62116, AS 3100 and AS 4777 |
Enclosure |
IP 65 |
DIMENSION |
W x H x D in cm. |
26.4 x 32.6 x 12 cm |
WEIGHT |
Approximate in kg. |
13 kg |