SPECIFICATIONS |
MODEL |
USV-1500 |
RATED POWER |
1500VA / 900W |
SYSTEM |
UPS system |
Digital line interactive UPS with Stabilizer |
Control system |
Microprocessor 8 bit
|
Stabilizer function |
Buck / Boost |
INPUT |
Input Voltage |
220 Vac ± 25%
|
Frequency |
50 Hz ± 10% (60 Hz ± 10%) auto sensing |
OUTPUT |
Voltage on AVR |
220 Vac ± 25%
|
Voltage on battery |
220 Vac, 50 / 60 Hz |
Wave form |
Pure sine wave |
PROTECTION |
Over voltage |
Mains to UPS backup 220Vac + 25% |
Under voltage |
Mains to UPS backup 220Vac - 25% |
Transfer time |
2 - 6 ms |
Overload (AC mode) |
Yes |
Overload (DC mode) |
Yes |
Output short circuit |
Software detection |
Surge energy dissipation |
312 Joules / 2 msec. |
Power dissipation |
1,000,000 W within 100 microsec. |
Acoustic noise |
Less than 55 dBA at 1 metre |
BATTERY |
Type |
Sealed lead acid (maintenance free) |
Backup time |
15 - 40 min. (depending on connected load) |
Continuous recharging time |
12 hours (90% after full discharged) |
OUTPUT OUTLET |
Number of backup outlets |
5 |
Number of surge protection outlet |
1 |
FEATURES |
AC / DC start |
Yes |
Communication interface |
USB port |
Monitoring and management software |
Free download Easy-Mon V software(1) at www.leonics.com |
Surge protection for telephone line |
Yes |
Surge protection for LAN line |
option |
Surge protection for laser printer |
Yes |
INDICATOR |
LCD display |
AC mode, Battery mode, Load level, Battery level,
Input voltage, Output voltage, Overload, Fault and Low battery
|
AUDIBLE ALARM (BUZZER) |
Battery mode |
Audible beep every 10 seconds |
Low battery |
Audible beep every second |
Overload |
Audible every 0.5 seconds |
Battery replacement |
Audible beep every 2 seconds (Battery test function on Easy-Mon V solftware) |
Fault |
Continuous beep |
ENVIRONMENT |
Temperature |
0 - 40ºC |
Relative humidity |
0 - 90% (non-condensing) |
CONFORMANCE |
Design regulation |
EMC category C2 |
DIMENSION |
W x H x D (mm.) |
145 x 220 x 367 |
WEIGHT |
Approximate in kg |
15 |